ACDC CWP1 230V 1A/5A AC/DC Current Monitor with Comparator
R476,20
- Description
Description
ACDC CWP1 230V 1A/5A AC/DC Current Monitor with Comparator
Protect equipment from over- and under-current conditions
The ACDC CWP1 is an 11-pin plug-in over/under current monitor for AC/DC loads. With fail-safe operation, fixed hysteresis and clear LED status, it compares measured current against adjustable trip limits and controls an SPDT relay for dependable protection.
Key Features
- Over/under current monitoring for AC/DC inputs
- Selectable input ranges via terminals: 0–1 A (pins 5 & 7) or 0–5 A (pins 6 & 7)
- SPDT relay: 10 A / 250 VAC
- Fail safe operation
- Startup delay: 10 seconds
- External latch input via link 8 & 9 (requires N.O. switch)
- LEDs: Green (relay energised), Red (overload fault), Red (underload fault)
- Hysteresis (trip recovery) fixed at 2% of tripping level
- Over/under load setpoints adjustable from 0–100%
- External potentiometer option: 10 kΩ
- Supply voltage (model variant): 230 VAC ±15% with galvanic isolation; isolation test voltage 2 kV
- Power consumption (AC): 1.5 VA
- Ambient temperature: −20°C to 70°C
- 11-pin plug-in module
How it works
On power-up, the CWP1 ignores the input current for a 10 s startup delay. The relay energises when current is within the user-set over and under thresholds. If current exceeds the over setpoint or drops below the under setpoint, the relay de-energises, and re-energises once the current passes the fixed 2% hysteresis. When latching is enabled, the relay remains de-energised until reset.
Installation Note
Install and wire according to the relevant connection diagram by a competent electrician.