Description

ACDC DET1 230VAC Defrost Timer 1C/O

Automate reliable defrost cycles in cold rooms

Maintain consistent temperatures and reduce ice build-up with an automated cooling/defrost sequence designed for cold room applications. The ACDC DET1 is microprocessor controlled for accuracy and repeatability, helping your system cycle efficiently without manual intervention.

How It Works

On power-up, the DET1 starts the cooling cycle. After the selected cooling interval, it switches to the defrost cycle, then returns to cooling—repeating this sequence until power is removed. An external thermostat can be used to terminate defrost early in the event of over-temperature.

Key Features

  • Supply: 230VAC model (AC versions feature galvanic isolation)
  • Selectable cooling cycle via DIP switches: 4, 6, 8 or 12 hours
  • Adjustable defrost duration: 1–60 minutes via front potentiometer
  • Relay output: 1 C/O (SPDT), 10A @ 250VAC
  • Microprocessor controlled for high repeat accuracy and fail-safe operation
  • Accuracy: range accuracy 0.5%, repeatability 0.1%, scale accuracy ±5%
  • Reset time: 300 ms
  • Operating temperature: -20 to +70°C
  • Power consumption (AC): 1.5 VA
  • LED indicators: Defrost ON (red), Fan ON (green)
  • External thermostat connection between terminals 5 & 6 terminates defrost on over-temperature
  • Optional link 5–6: start with a defrost cycle first
  • Standard 11-pin base mounting
  • Typical application: cold rooms requiring regular coil defrosting
  • Terminal guidance (DET1): compressor and fan to terminal 4; defrost heater to terminal 3; common supply to terminal 1