Description
CBI CQF6340O QF-3(26) 40A 3-Pole 6 kA Circuit Breaker (Orange Handle)
Reliable 3‑phase protection that stays consistent across temperatures
Hydraulic‑magnetic technology delivers precise, temperature‑independent tripping—ideal where stable protection and fast reset are essential.
Key Features
- Current rating: 40 A
- Poles: 3‑pole
- Short‑circuit capacity: 6 kA
- Operating voltage (3‑pole): 415 Vac
- Time delay: Curve 1 (long time delay, high instantaneous trip 10–20 × In), Orange handle
- Technology: Hydraulic‑magnetic; 100% rating capability independent of ambient temperature
- Mounting: Dual DIN & mini rail with 57 mm front escutcheon (black)
- Isolation: Suitable for electrical isolation
- Indication: Trip indication with mid‑trip position
- Terminals: Box terminals up to 50 mm²; wire size 2.5–25 mm²; 4 Nm torque
- Width: 78 mm (3 modules; 26 mm per pole)
- Operating temperature: −40 °C to +85 °C
- Impulse withstand: 6 kV
- Endurance: 10,000 operations (1,500 electrical at rated current and voltage)
- Compliance/approvals: VC 8036 (SANS/IEC 60947‑2), CE, CCC; GB 14048.2
Applications
- AC branch circuit protection (DIN/EN 60947‑2)
- Telecom/datacom equipment
- Lighting control
- UPS equipment
- Alternative energy equipment
- Mobile power generation equipment
- Railway signalling equipment
- Residential and industrial equipment
Documentation